Copley Controls 87
CHAPTER
9: FAULTS
This chapter shows how to configure the amplifier’s fault latching. Perform the basic steps
outlined below. Details follow in the chapter:
1
Click Configure Faults to open Faults Configuration screen.
2
Select the faults to latch. See Fault Configuration Parameters (p. 88).
3
Click OK to close screen and save changes to amplifier RAM.
4
On the Main screen, click Save to Flash to avoid losing the changes.
!
DANGER
Risk of unexpected motion with non-latched faults.
After the cause of a non-latched fault is corrected, the amplifier re-enables
the PWM output stage without operator intervention. In this case, motion
may re-start unexpectedly. Configure faults as latched unless a specific
situation calls for non-latched behavior. When using non-latched faults, be
sure to safeguard against unexpected motion.
Failure to heed this warning can cause equipment damage, injury, or
death.